EVAPORATING COOLER

The evaporating condensers are equipment for condensation, subcooling of refrigerant gases and for cooling of liquids or gases such as water or air.

Name : CE A18 F
CE: Evaporating Cooler
A: Type of serpentine
18: Amount of serpentines
F: Freon
N: Amonia

DESIGN AND MANUFACTURING
When designing the condenser the focus has been on a combination of low operating weight and high rigidity. Condensers are built in heavy steel sheets with antirusting treatment and galvanized steel sheets.
The condenser has two parts: one where the serpentine, nozzles for water distribution and fluid collectors are and another for tank and water pump. The whole structure is compact, making it easy to install and highly effective.
All parts are easy to maintain, not being necessary desassemble any door, lid or structure to access to them. The water tank has the dimensions to store the volume required by the equipment. No extra tank is necessary. The serpentine is make of steel pipe of 50 kg/cm2 of resistance, bent in cold and later galvanized by bathing them in hot zinc, tested to 25 kg/cm2.
The serpentines can be divided into one, two or more parts for different condensing circuits, with one part for water cooling of compressors, eliminating formation of incrustations in water system. Where room temperature is below water freezing temperature, it is imposible to add antifreezing liquids into the system such as glicoles.
The water distribution system has no-plugging nozzles on zinc antirusting collectors, distributing the amount of water required to keep the therrmic exchange surface constantly wet. The water distribution system does not need any adjustment. The section of drop eliminators is built rigidly in galvanized steel sheets entirely. Its location no the upper part of the equipment allows easy reach to nozzle
The forcers are axial type, assembled on the water deposit, easy to reach on floor level. The electric motors are 100% pretected against water or dust.
The water tank in heavy steel sheet is rust protected with zinc. The water level is constant by a high pressure floating valve. A suction filter makes it impossible for particles to be impulsed by the pump towards the nozzles. There is emptying conection, continum water purge and purge by stopping the equipment.
The water pump is monoblock type, 100% shielded, joined to the water trank by a pass valve.

 

TECHNICAL SPECIFICATIONS


 

 

 

 

 

 

MOD.

CAPACITY

DIMENSIONS ( mm )

FORCERS

WATER PUMP

VOLUMEN

WEIGHT

KW

Kcal/h x1000

A

B

C

Cant.

CV

Cant.

CV

metros3

Kg.

CEA 22

91.9

79

2400

730

2600

2

1

1

1

4.2

1.000

CEA 26

108.1

93

2400

860

2600

2

1.5

1

1

5

1.200

CEA 32

125.6

108

2400

980

2600

2

1.5

1

1

5.5

1.300

CEA 38

151.2

130

2400

1200

2600

2

2

1

1.5

6.2

1.500

CEA 46

182.6

157

2400

1400

2600

2

2

1

1.5

8.2

1.800

CEA 54

212.8

183

2400

1700

2600

2

2

1

1.5

11.5

2.900

CEB 39

290

250

3500

1300

2900

3

2

1

2

13.2

3.200

CEB 48

357

307

3500

1600

2900

3

3

1

3

16.3

3.700

CEB 56

418.6

360

3500

1850

2900

3

3

1

3

18.8

4.000

CEB 65

483.7

416

3500

2150

2900

3

3

1

3

22

4.300

CEC 52

531.4

457

4600

1750

3100

4

3

1

4

25

4.800

CEC 56

560.5

482

4600

1850

3100

4

3

1

4

26.5

5.000

CEC 60

600

516

4600

2000

3100

4

3

1

4

28.7

5.300

CEC 65

650

559

4600

2150

3100

4

4

1

7.5

31

5.600

CEC 70

700

602

4600

2300

3100

4

4

1

7.5

33

5.900

CEC 75

750

645

4600

2500

3100

4

4

1

7.5

36

6.200

CEC 84

839.5

722

4600

2750

3100

4

5.5

1

10

40

7.300

CEC 90

901.2

775

4600

3000

3100

4

5.5

1

10

43

9.000

T.cond.= + 35ºC. - T.bh= + 24ºC.